CVE-2022-30315

CriticalCVSS 9.8/10Last modified Jun 17, 2026

Description

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

Metrics

CVSS 3.1 9.8/10CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Weakness enumeration

Affected software

No affected versions have been published.

Timeline

Published
Jul 28, 2022
Last modified
Jun 17, 2026
NVD status
Modified

Related CVEs from 2022

CVE-2022-303166.8Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a HoneyCVE-2022-303179.1Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a HoneyweCVE-2022-303189.8Honeywell ControlEdge through R151.1 uses Hard-coded Credentials. According to FSCT-2022-0056, there is a Honeywell ControlEdge hardcoded crCVE-2022-303198.1Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess ControCVE-2022-30326.5When receiving an HTML email that contained an <code>iframe</code> element, which used a <code>srcdoc</code> attribute to define the inner HCVE-2022-303204.3Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a SCVE-2022-303218.6go-getter up to 1.5.11 and 2.0.2 allowed arbitrary host access via go-getter path traversal, symlink processing, and command injection flawsCVE-2022-303228.6go-getter up to 1.5.11 and 2.0.2 allowed asymmetric resource exhaustion when go-getter processed malicious HTTP responses. Fixed in 1.6.1 anCVE-2022-303238.6go-getter up to 1.5.11 and 2.0.2 panicked when processing password-protected ZIP files. Fixed in 1.6.1 and 2.1.0.CVE-2022-303249.8HashiCorp Nomad and Nomad Enterprise version 0.2.0 up to 1.3.0 were impacted by go-getter vulnerabilities enabling privilege escalation throCVE-2022-303258.8An issue was found on TRENDnet TEW-831DR 1.0 601.130.1.1356 devices. The default pre-shared key for the Wi-Fi networks is the same for everyCVE-2022-303265.4An issue was found on TRENDnet TEW-831DR 1.0 601.130.1.1356 devices. The network pre-shared key field on the web interface is vulnerable to
CVE-2022-30315: Critical severity, CVSS 9.8 | Vulnix