Description
Motorola ACE1000 RTUs through 2022-05-02 mishandle application integrity. They allow for custom application installation via either STS software, the C toolkit, or the ACE1000 Easy Configurator. In the case of the Easy Configurator, application images (as PLX/DAT/APP/CRC files) are uploaded via the Web UI. In case of the C toolkit, they are transferred and installed using SFTP/SSH. In each case, application images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
Metrics
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:HWeakness enumeration
Affected software
| Vendor | Product | Versions |
|---|---|---|
| n/a | n/a | n/a |
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-06Mitigation, Third Party Advisory, US Government Resource
- https://www.forescout.com/blog/Not Applicable
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-06Mitigation, Third Party Advisory, US Government Resource
- https://www.forescout.com/blog/Not Applicable
Timeline
- Published
- Jul 26, 2022
- Last modified
- Jun 17, 2026
- NVD status
- Modified