Description
A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
Metrics
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HWeakness enumeration
Affected software
No affected versions have been published.
Timeline
- Published
- Dec 1, 2025
- Last modified
- Sep 26, 2026
- NVD status
- Analyzed