Description
Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user.
Metrics
CVSS 3.1 8.6/10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:HWeakness enumeration
Affected software
| Vendor | Product | Versions |
|---|---|---|
| n/a | Rockwell Automation MicroLogix 1400 | MicroLogix 1400, All series Version 21.6 and below |
References
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1129877/loc/en_US#__highlightPermissions Required, Vendor Advisory
- https://us-cert.cisa.gov/ics/advisories/icsa-21-033-01Third Party Advisory, US Government Resource
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1129877/loc/en_US#__highlightPermissions Required, Vendor Advisory
- https://us-cert.cisa.gov/ics/advisories/icsa-21-033-01Third Party Advisory, US Government Resource
Timeline
- Published
- Mar 25, 2021
- Last modified
- Jun 17, 2026
- NVD status
- Modified