Description
A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V10, V11, V12 (All versions), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V13 (All versions < V13 SP2 Update 2), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V14 (All versions < V14 SP1 Update 6), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V15 (All versions < V15 Update 2). Improper file permissions in the default installation of TIA Portal may allow an attacker with local file system access to manipulate resources which may be transferred to devices and executed there by a different user. No special privileges are required, but the victim needs to transfer the manipulated files to a device. Execution is caused on the target device rather than on the PG device.
Metrics
CVSS:3.0/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:HWeakness enumeration
Affected software
| Vendor | Product | Versions |
|---|---|---|
| Siemens AG | SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V10, V11, V12, SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V13, SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V14, SIMATIC STEP 7 (TIA Po | SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V10, V11, V12 : All versions; SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V13 : All versions < V13 SP2 Update 2; SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V14 : All versions < V14 SP1 Update 6; SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V15 : All versions < V15 Update 2 |
References
- http://www.securityfocus.com/bid/105115Third Party Advisory, VDB Entry
- https://cert-portal.siemens.com/productcert/pdf/ssa-979106.pdfVendor Advisory
- http://www.securityfocus.com/bid/105115Third Party Advisory, VDB Entry
- https://cert-portal.siemens.com/productcert/pdf/ssa-979106.pdfVendor Advisory
Timeline
- Published
- Aug 7, 2018
- Last modified
- Jun 17, 2026
- NVD status
- Modified