CVE-2023-1133

CriticalCVSS 9.8/10Last modified Jun 17, 2026

Description

Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code.

Metrics

CVSS 3.1 9.8/10CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Weakness enumeration

Affected software

No affected versions have been published.

Timeline

Published
Mar 27, 2023
Last modified
Jun 17, 2026
NVD status
Modified

Related CVEs from 2023

CVE-2023-11348.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a path traversal vulnerability, which could allow an attaCVE-2023-11357.8In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could set incorrect directory permissions, which could reCVE-2023-11367.5In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an unauthenticated attacker could generate a valid token, which wouldCVE-2023-11378.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which a low-level user could extract files andCVE-2023-11387.5Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain an improper access control vulnerability, which could allow an atCVE-2023-11398.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-gateCVE-2023-11409.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability that could allow an attacker to achieve unauthentCVE-2023-11418.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a command injection vulnerability that could allow an attacker toCVE-2023-11429.8In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use URL decoding to retrieve system files, credentiCVE-2023-11438.8In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use Lua scripts, which could allow an attacker to rCVE-2023-11448.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contains an improper access control vulnerability in which an attacker caCVE-2023-11457.8Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-Data
CVE-2023-1133: Critical severity, CVSS 9.8 | Vulnix