CVE-2021-27391

CriticalCVSS 9.8/10Last modified Jun 17, 2026

Description

A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.

Metrics

CVSS 3.1 9.8/10CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Weakness enumeration

Affected software

VendorProductVersions
SiemensAPOGEE MBC (PPC) (P2 Ethernet)All versions >= V2.6.3
SiemensAPOGEE MEC (PPC) (P2 Ethernet)All versions >= V2.6.3
SiemensAPOGEE PXC Compact (BACnet)All versions < V3.5.3
SiemensAPOGEE PXC Compact (P2 Ethernet)All versions >= V2.8
SiemensAPOGEE PXC Modular (BACnet)All versions < V3.5.3
SiemensAPOGEE PXC Modular (P2 Ethernet)All versions >= V2.8
SiemensTALON TC Compact (BACnet)All versions < V3.5.3
SiemensTALON TC Modular (BACnet)All versions < V3.5.3

References

Timeline

Published
Sep 14, 2021
Last modified
Jun 17, 2026
NVD status
Modified

Related CVEs from 2021

CVE-2021-273928.8A vulnerability has been identified in Siveillance Video Open Network Bridge (2020 R3), Siveillance Video Open Network Bridge (2020 R2), SivCVE-2021-273935.3A vulnerability has been identified in Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2013.08), Nucleus Source Code (VerCVE-2021-273948.8A vulnerability has been identified in Mendix Applications using Mendix 7 (All versions < V7.23.19), Mendix Applications using Mendix 8 (AllCVE-2021-273958.1A vulnerability has been identified in SIMATIC Process Historian 2013 and earlier (All versions), SIMATIC Process Historian 2014 (All versioCVE-2021-273967.8A vulnerability has been identified in Tecnomatix Plant Simulation (All versions < V16.0.5). The PlantSimCore.dll library lacks proper validCVE-2021-273977.8A vulnerability has been identified in Tecnomatix Plant Simulation (All versions < V16.0.5). The PlantSimCore.dll library lacks proper validCVE-2021-273987.8A vulnerability has been identified in Tecnomatix Plant Simulation (All versions < V16.0.5). The PlantSimCore.dll library lacks proper validCVE-2021-273997.8A vulnerability has been identified in Simcenter Femap 2020.2 (All versions < V2020.2.MP3), Simcenter Femap 2021.1 (All versions < V2021.1.MCVE-2021-274007.5HashiCorp Vault and Vault Enterprise Cassandra integrations (storage backend and database secrets engine plugin) did not validate TLS certifCVE-2021-274016.1The Join Meeting page of Mitel MiCollab Web Client before 9.2 FP2 could allow an attacker to access (view and modify) user data by executingCVE-2021-274026.5The SAS Admin portal of Mitel MiCollab before 9.2 FP2 could allow an unauthenticated attacker to access (view and modify) user data by injecCVE-2021-274036.1Askey RTF8115VW BR_SV_g11.11_RTF_TEF001_V6.54_V014 devices allow cgi-bin/te_acceso_router.cgi curWebPage XSS.
CVE-2021-27391: Critical severity, CVSS 9.8 | Vulnix