Description
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.
Metrics
CVSS 3.1 7.5/10
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HWeakness enumeration
Affected software
| Vendor | Product | Versions |
|---|---|---|
| Siemens AG | SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules | All versions |