Description
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.
Metrics
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HWeakness enumeration
Affected software
No affected versions have been published.
Timeline
- Published
- Mar 10, 2020
- Last modified
- Jun 17, 2026
- NVD status
- Modified